ZP752-2 LINE SOUNDER DRIVER

  • Two monitored sounder circuits
  • Support for 3s response from manual call points
  • Addressable – connects to ZP loop
  • Programmable for continuous or pulsed output

Description

The ZP752-2 is a loop wired interface providing two conventional alarm circuits. It may programmed to operate from a single address, a group or zone of devices or as a common output, from any trigger device connected to the system.
Power for the alarm circuits is supplied either from an external power supply unit, or directly from the panel’s 24VDC supply via separate wiring. The ZP752-2 monitors its power supply and failure is reported to the main control panel automatically.

Any number of ZP752-2 units (up to a max of 127) can be connected to the ZP loop. In systems complying with the recommendations of BS5839-1, where sounder response to the operation of a manual call point must be within 3 seconds, up to 16 ZP752-2 output units, assigned to the first 16 addresses on each loop can be operated within the time period.

Ordering

13810-ZT Ziton ZP752-2  Addressable loop interface unit for 2 conventional alarm circuits

ZP752-2 datasheet